Input Data
Sections 3.3.2.2 β 3.3.2.4Location
Tank Volume
mΒ³
Calculate from geometry
Orientation
Head Type
m
m
m
For vertical cylindrical tanks, volume based on shell height is acceptable (Β§3.3.2.3.1).
Insulation & Wall Construction
Ri reduces thermal inbreathing (Eq. 9) and thermal out-breathing (Eq. 7). No insulation = Ri = 1.0.
Tank is insulated?
Insulation type
Insulation material properties
Rin = 1 / (1 + hΒ·lin/Ξ»in) [Eq. 11]
m
W/mΒ·K
W/mΒ²Β·K
Double wall tank?
Double Wall Eq. 13
%
Rc = 0.25 + 0.75Β·(Ac/A) [Eq.13]
Liquid Discharge Eq. 5
V̇ip = V̇pe [Eq. 5] — direct, no correction needed
m³/h
Β°C
Thermal Inbreathing Eq. 9
VΜIT = C Β· Vtk0.7 Β· Ri [Eq. 9]
Liquid Filling Eq. 1 / 3
Non-volatile (Vp ≤ 5 kPa): V̇op = V̇pf [Eq. 1]
Volatile (Vp > 5 kPa): V̇op = 2.0 · V̇pf [Eq. 3]
m³/h
Β°C
Flashing liquid (Β§3.3.2.2.1c): If the entering liquid flashes upon entering the tank, perform a separate equilibrium flash calculation and add the resulting vapor generation to the out-breathing requirement. No simplified formula is provided in API 2000 for this case.
Thermal Out-breathing Eq. 7
VΜOT = Y Β· Vtk0.9 Β· Ri [Eq. 7]
β
Y-factor is set automatically from your latitude selection. Table 1: <42Β° β 0.32 Β· 42β58Β° β 0.25 Β· >58Β° β 0.20
Method Selection Β§3.3.3.3.3
Β§3.3.3.3.3: Where the stored fluid's properties are similar to hexane, the required venting capacity can be read directly from Table 5/Table 7 (ATWS < 260 mΒ²) or Eq. 16 (ATWS ≥ 260 mΒ², P > 7 kPa) β no need to evaluate L, T, or M individually. For diesel or other fluids that differ meaningfully from hexane (e.g. much higher latent heat, different molecular mass), use the general Eq. 14 route instead.
Wetted Surface & Heat Input Table 3
q = 906.6 · (Q·F/L) · (T/M)0.5 [Eq. 14]
m²
kPa(g)
Calculate ATWS from tank geometry
Tank configuration Table 5 note a
ATWS = πD · min(H, 9.14) β excludes roof & bottom plate
m
m
Table 3 β Heat Input Q (SI): <18.6 m² → 63,150·ATWS · 18.6–93 m² → 224,200·ATWS0.566 · 93–260 m² → 630,400·ATWS0.338 · ≥260 m² & P>7 kPa → 43,200·ATWS0.82 · ≥260 m² & P≤7 kPa → 4,129,700 W (capped — Β§3.3.3.3.3 / Annex B).
Environmental Factor Table 9
β
Only one environmental factor may be credited (Β§3.3.3.3.4). Insulation must resist dislodgment by fire-fighting equipment and not decompose below 537.8 Β°C (1000 Β°F) β Table 9 note a.
Vapor Properties at Relieving Conditions Eq. 14
J/kg
Β°C
β
Defaults shown (334,900 J/kg, 15.6 Β°C, M=86.17) are hexane at atmospheric pressure. For diesel, typical relieving-condition values are much higher latent heat (~250,000β260,000 J/kg) and higher molecular mass (~170β200) β replace with your own fluid data at relieving conditions.
Results
Β§3.3.1 Summary
Enter data and press Calculate.
Quick Reference
Tables 1 & 2Y-factor β Table 1
| Latitude | Y |
|---|
C-factor β Table 2
| Lat. | Hex<25Β°C | Hexβ₯25Β°C | Higher |
|---|
"Higher/unknown" C-factor applies when vapor pressure > hexane or is unknown, regardless of temperature.